3-PHASE HYDRO 5% WIRE LOSS CHART

Distance one-way in feet of three conductor copper wire

WATTS #14 #12 #10 #8 #6
500/120V 810 1360 2125 3375 5435
1000/240V 500 875 1375 2250 3625
1500/240V 375 600 875 1500 2375
3000/240V 225 350 600 900 1425
 

Less than 5% wire loss is ideal; 10% loss is normal; but up to 50% or more loss is acceptable where sufficient water is available.

If wire loss or cost become excessive (wire size >#8 and cost >$500), consider ordering the high voltage model (440V), which can go twice the distance using the same size wire.

Example:

If you have 70gpm with 65psi, producing 1000Watts, you could go 875 feet using 12 gauge wire with a 5% loss, or 1750 feet with a 10% loss, or 1750 feet with a 5% loss using the high voltage model (440V).

Most houses find 400W more than adequate power (=9.6KW/day) and end up dumping the extra power into resistors. If 500W is sufficient, in the above example, you could go 17500 feet (10 x 5 = 50% loss @ 440V) and still have ample power.

UF or USE wire is made for outdoor direct-burial and is available, in single or three strands together, romex-style, 1000' rolls, in sizes 12/3 and 8/3.

COPPER WIRE RESISTANCE
WIRE GAUGE
DIAMETER INCHES
OHMS PER 1000'
OHMS PER MILE
0000
0.460
0.05
0.26
000
0.410
0.06
0.33
00
0.364
0.08
0.42
0
0.324
0.10
0.52
2
0.258
0.16
0.84
4
0.204
0.25
1.34
6
0.162
0.40
2.13
8
0.128
0.64
3.38
10
0.102
1.02
5.38
12
0.081
1.62
8.56
14
0.064
2.58
13.6
16
0.051
4.10
21.6
18
0.040
6.52
34.4
Return to Data